11.Warning
!
Assemble tool
Do not poke the port
!
Do not pull the cable
Wire conductors must not be exposed to avoid any shortage from the conductor end.
!
WARNING
02
1.DPC-10 Panel introduction
2.Technical data
Supply voltage: 110-230Vac ± 10% 50/60HZ
Maximum ambient temperature: +40
℃
Maximum liquid temperature: +65
℃
Maximum system pressure: 10bar
Maximum contact load AMP: 12A
Ingress Protection Rating: IP55
Model Number
LED Light
LCD Display
Technical Data
Button
Pressure Unit
»
»
»
»
»
»
» Relay Capacity: 1HP in 110V or 2HP in 230V
» The digital pressure controller can control pump with
higher output through a contactor with control circuit
voltage of 110Vac or 230Vac, in the other hand, the
supply voltage to DPC is 110Vac or 230Vac 50/60hz,
please refer to the wiring diagram for requirement.
Dry Running
Digital Pressure Controller
DPC-10
Over Pressure
bar
kg/cm
2
psi
Power :110-230Vac±10% 50/60HZ
Max :12A / Max :10bar / IP55
3.Wiring diagram
Incorrect wiring could cause damage to the pressure controller,
confirm the color of the wires with the operation manual before wiring.
04
a. Single phase wiring connection
b. Three phase wiring connection-230V
c. Three phase wiring connection-380V
3 phase PUMP
M1
U V W
3
3W AC 230V
R S T
3 phase PUMP
M1
DPC-10
Controller
Gray
Brown
Blue
Black
U V W
3 4W AC 380V
R S T N
NFB
(MCCB)
AC 230V
M1
Coil
If connecting to a pump driven by 3ph/380V pump (Please
AC 110V,230V
NFB
(MCCB)
1
NFB
(MCCB)
L N
If installing DPC-10 with a varistor, please connect varistor wire in parralled with
thin Brown and Blue wires of the DPC-10.
*
note the power voltage must not exceed 400V.), the blue wire must not
connect to R or S wire, otherwise the DPC-10 controller will be burned out.
220V( <250V)
Note: If the voltage is over 250V, please add transformer by yourself.
DPC-10
Controller
Gray
Brown
Blue
Black
AC 230V
M1
Coil
DPC-10
Controller
Gray
Brown
Blue
Black
1 phase PUMP
WARNING
!
WARNING
!
WARNING
!
Any connection to the contactor, please add a
R.C capacitor (spark eliminator) to reduce the
possible electromagnetic interference.
WARNING
!
Beware of any connection to the contactor.
Please add a R.C. capacitor (spark eliminator) to
reduce the possible electromagnetic interference.
4.Button Function Introduction
Button Icon
Function
Browsing original pressure value.
Downward adjustment of the parameter value.
Pump start and stop operation
Upward adjustment of the parameter value.
Possible with Button
Short press once:
Switch to Basic parameter setting
Hold down the botton for 3 seconds:
Switch to Advance parameter setting
After entering the parameter setting,short press once again:
Switch to next setting mode and enter the set value
Long press for 6 seconds to Lock/Unlock the SET button for privacy.
06
“ ” (Short press once to enter Basic Setting Mode)
Setting procedure :
Max. pressure
→
Min. start pressure
→
Time-Delay
Item Parameters Display
Code
Default
Unit
Data
Range
P-max kg/cm² 0.01-
10.00
Description
Max. pressure
setting
(high pressure)
a.Select to modify Max. Pressure, press the
left or right button to adjust the value, after
finishing the setting, press the SET button
once and go to Min. start pressure
1
0-60
kg/cm²
sec
-
-
P-min
Delay
loAd
Min. start
pressure setting
(low pressure)
Time-Delay
setting when
reaching the
Max. Pressure
Load for 3
seconds to store
setting value
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the pressure, press
the SET button, and go to next parameter
setting.
a.Select to modify Min. start pressure , press
the left or right button to adjust the value,
after finishing the setting, press the SET
button once and go to Time-Delay setting .
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c. Choose not to modify the pressure, press
the SET button, and go to next parameter
setting.
a.Select to modify the Time-delay setting
when reaching the Max. Pressure, press
the left or right button to adjust the value,
after finishing the setting, press the SET
button and go to " loAd " display.
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the delay time, press
the SET button, and LCD display " loAd "
The above setting value is stored and after
3 seconds will automatically return to the
current pressure value.
2
3
4
setting.
0.01-
10.00
5.The status of LED lights
6.Parameter display and settings
Item
Light
Message indication
Control loop off from the system
Non
Green
Orange
Red
Pump status
Control loop commands the system
pump to start running
Control loop is loaded into the system
Warning message to shut down the
system temporarily
Pump off
Pump on
Pump standby
Pump auto stop and display
the fault message (Dry running
1
2
3
4
Item Parameter Display
Code
Default
Unit
P-max kg/cm²
kg/cm²
kg/cm²
P-min
P-Dry
Description
Pressure of
water shortage
setting display
(Dry running)
Min. Pressure
setting display
Max. Pressure
setting display
» Press once: To see the Max. pressure setting value.
» Or stay on this screen for 5 seconds it will automatically
return to the current pressure status display.
» Press again: To see the Min. pressure setting value.
» Or stay on this screen for 5 seconds it will automatically
return to the current pressure status display.
» Press again: To see the pressure of water shortage
setting value.
» Or stay on this screen for 5 seconds it will automatically
return to the current pressure status display.
1
2
3
“ ” (Pressure value display)
or Over pressure)
Item Parameter Pump action
Description
Stop (OFF)
Restart (ON)
Pump off
Non
Pump on
Orange Press once to restart the pump running.
Hold down for 3 seconds to stop the pump
1
2
“ ” (Restart or stop the pump running)
running.
Light
Lock/Unlock
Setting function
kg/cm²
Long press for 6 seconds (Lock/Unlock the SET button)
“ ” Hold down for 3 seconds (Advanced setting Mode)
Item Parameters Display
Code
Default
Unit
Data
Range
Unit
-
-
Description
Switch the
display working
pressure unit
a.Select to switch the Unit of working
pressure, press the right button to change
the pressure unit (Cycle : kg/cm²
→ Psi
→ bar →
kg/cm²), then press the SET
button once and go to next parameter
setting.
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the working pressure
unit, press the SET button once, and go
to next parameter setting.
1
P-Dry
sec 1-120
0.01-
10.00
P-Dry
Detection time
setting of water
shortage
Pressure of
water shortage
setting
(Dry running)
a.Select to modify the detection time after
reaching the pressure setting of water
shortage (Dry running), press the left or
right button to adjust the value, after
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify P-Dry detection time
setting, press the SET button once, and
go to next parameter setting.
a.Select to modify the Pressure of water
shortage, press the left or right button to
adjust the value, after finishing the setting,
press the SET button and go to next
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the pressure of water
shortage, press the SET button, and go
to next parameter setting.
2
3
0-600
sec
hour
Auto
Reset
Auto
Time setting of
automatic
re-start running
after warning
shutdown (Dry
running or
Over pressure)
(
α
value)
Auto shutdown
setting after
continuous
running
a.Select to modify automatic re-start time,
press the left or right button to adjust the
value, after finishing the setting, press the SET
button, and go to next parameter setting.
The time of automatic re-start = (automatic
time setting) x (trip times)³
(Cumulative trip times is up to 10 times, if
pressing the right button to re-start, then the
trip times can be re-calculated.)
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the automatic re-start
time, press the SET button, and go to next
parameter setting.
a.Select to modify the auto shutdown setting
after continuous running, press the left or
right button to adjust the value, after finish-
ing the setting, press the SET button and
go to next parameter setting.
St-0:
Pressure controller keeps running
and won’t shut down automatically.
St-.5:
Pressure controller will auto shut
down after continuously running 0.5 hours
and won’t auto restart after the shutdown.
St-1-5:
Pressure controller will auto shut
down after continuously running 1-5 hours
and won’t auto restart after the shutdown.
4
5
finishing the setting, press the SET button
kg/cm²
parameter setting.
Item Parameters Display
Code
Default
Unit
Data
Range
Description
and go to next parameter setting.
St-0
St-.5
St-1
-
St-5
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to modify the automatic re-start
time, press the SET button, and go to next
parameter setting.
08
7.Standard default value (Factory preset settings)
10
8.Setting value range
a. Pressure setting range : 0.01 - 10.00bar
b. Time-Delay setting range : 0 - 60 seconds
c. Detection time after Dry-running setting range: 1-120 seconds
d. Time of automatic re-start running after warning shutdown
(α value) setting range : 0 600 seconds
e. Auto shutdown setting range: None and 0.5-5Hours
a. Max. pressure value : 2.5 kg/cm²
b. Min. pressure value : 1.5 kg/cm²
c. Delay Time when reaching the Max. Pressure : 15 seconds
d. The pressure unit : kg/cm²
e. Detection time of water shortage : 30 seconds
f. Pressure of water shortage : 0.5 kg/cm²
g. Time of automatic re-start running after warning shutdown
(α value) : 60 seconds
h. Auto shutdown setting after continuous running : St-0
i. Over pressure value is fixed in 10bar and cannot modify
-
-
dF-n
dF-y
-
-
- - - -
or
loAd
Restore to
default value
setting
LCD screen
display “loAd”
or “ ----” for 3
seconds to
store and finish
the setting
a.Select to restore default value settings
(dF-y), press the right button and adjust the
parameter value from dF-n to dF-y.
After finishing the setting, press the SET
button, then all the advanced value
settings are returned to default value.
LCD screen will display "- - - -" for 3 seconds
and return to the current pressure conditions.
b.Stay on this screen for 30 seconds, the
display screen will automatically return to
the current pressure conditions and the
preset data value will not be stored.
c.Choose not to return to default value
settings (dF-n), select dF-n and press the
SET button again, LCD screen display
"loAd" for 3 seconds and will
return to the
After LCD screen displaying “loAd” or “ ----”
for 3 seconds, above setting value is stored
and it will automatically return to the current
pressure value.
6
7
Item Parameters Display
Code
Default
Unit
Data
Range
Description
current pressure conditions automatically.
9.The current operating parameters display
1).Max. pressure setting display
(high pressure) (Show code P-max)
2).Min. start pressure setting display (low pressure) (Show code P-min)
↓ Press once
a-1. Press once to browse original pressure value
↓ Press once
3).Pressure of water shortage setting display (Dry running)
(Show code P-Dry)
↓ Press again
12
1).Lock the SET button after long press for 6 seconds
(Show code )
2).Unlock SET button after long press again for 6 seconds
(Show code UnL)
a-2. Long Press for 6 seconds to Lock/Unlock the SET button
1).Max. pressure setting (high pressure) (Show code P-max)
b. Press once to enter basic setting
Press
to adjust the value upward
Press
to adjust the value downward
2).Min. Start pressure setting (low pressure) (Show code P-min)
↓ Press once
Press
to adjust the value upward
Press
to adjust the value downward
↓ Press once
14
1).Change the display working pressure unit (Show code Unit)
3).Time-Delay setting after reaching the Max. Pressure
(Show code Delay)
4).All parameter settings is stored (Show code loAd)
c. Press for 3 seconds to enter advanced setting
Press
to adjust the value upward
Press
to adjust the value downward
↓
Press once
↓
3 seconds later
5).After finishing above setting, 3 seconds later will return to the
current pressure status display automatically.
Press to set up unit
Cycle of working pressure unit:
kg/cm²
→
psi
→
bar
→
kg/cm²
↓
Press once
16
2).Detection time setting of water shortage
(Show code P-Dry & sec)
3).Pressure of water shortage setting (Show code P-Dry)
5). Auto shutdown setting after continuous running
(Show code Aut
o)
Press
to adjust the value upward
Press
to adjust the value downward
↓ Press once
4).Time setting of automatic re-start running after warning shutdown
(Dry running or Over pressure) (α value) (Show code Auto reset)
Press
to adjust the value upward
Press
to adjust the value downward
↓ Press once
Press
to adjust the value upward
Press
to adjust the value downward
↓ Press once
» St-0: Pressure controller keeps running and will not automatically
shut down.
St-.5&St-1-5: Pressure controller will auto shut down after
continuously running 0.5 or 1-5 hours and will not automatically
restart after the shutdown.
»
Press
to adjust the value upward
Press
to adjust the value downward
↓ Press once
When the pressure controller
displays "EEEE" the pressure
sensor has failed.
When the pressure controller
displays "FFFF" the temperature
sensor has failed.
When the pressure controller
displays "EEFF" the pressure and
temperature sensor have failed.
b).FFFF
c).EEFF
a).EEEE
10.Fault Display
18
6).Restore to default value setting or not
To restore default value settings (show code dF-y)
»
Press to adjust the value to dF-y
Press once and restore to default value (Show code ----)
7).After finishing above settings, LCD screen display “loAd” or “ ----”
3 seconds later, above setting value is stored and it will
automatically return to the current pressure value.
Not to restore default value settings (show code dF-n)
»
Press to set the value to dF-n
Press once then all settings are stored. (Show code loAd)