Instruction Manual

 

 

 

 

 

MPR-E1 V2.0 

Motor Protection Relay 

  

                                         

 

                            

 

                                                                      

                                                            

EAPL

 

 

 

Introduction 

Self powered device, Displays 3 Phase voltage, current and frequency 
during healthy condition. 
Monitors and control Phase failure, Phase unbalance, Phase Reversal, over 
voltage, under voltage, over current, under current, over frequency, under 
frequency and Earth Leakage in 3 Phase 4 wire system. 

 

 

 

 

 

 

 

 

 

 

 

 

    
  
 

 Box Accessories

 

 One (1) MPR-E1 V2.0  Monitoring Device         
 One (1) Instruction Manual 
 One (1) RC Filter 

 

PARAMETERS 

 IN VOLTAGE, 

CURRENT AND 

FREQUENCY

 

R-V

 

 

 

 

Y-V

 

 

 

 

B-V

 

 

 

 

RY-V

 

 

 

 

YB-V

 

 

 

 

BR-V

 

 

 

 

R-A 

Y-A 

B-A 

Hz 

 

 
Safety Precautions

 

Read and follow all the safety precautions and instructions before 
installing and working with the equipment. 

                         !   

DANGER 

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH 

 

Apply appropriate personal protective equipment(PPE) and follow 
safety work practices 

 

Only qualified electrical workers should install this equipment. Such work 
should be performed only after reading this entire set of instructions. 

 

If the equipment is not used in the manner specified by the 
manufacturer, the protection provided by the equipment may be 
impaired. 

 

NEVER work alone. 

 

Turn OFF all power supplying the monitoring device and the equipment 
in which it is installed before working on it. 

 

The successful operation of this equipment depends upon proper 
handling, installation and operation. Neglecting fundamental installation 
requirements may lead to personal injury as well as damage to 
electrical equipment or other property. 

 

NEVER bypass external fusing. 

 

NEVER apply the voltages at Program Lock and Auto Reset terminals. 

 

Before performing Dielectric or Megger testing on any equipment in 
which the monitoring device is installed, disconnect all the input and 
output wires to the monitoring device. High voltage testing may 
damage electronic components contained in the monitoring device. 

 

The monitoring device should be installed in a suitable electrical 
enclosure. 

 Failure to follow these instructions will result in death or serious injury. 

 

EAPL is not responsible for any consequential damages arising out of use 
of our products, though the technology is cautiously chosen and 
implemented like any other well designed good electric device.  

Installation

 

Connecting cable recommendations

 

 

 

Insulation rating 

Current rating 

Voltage circuit 

>600 VAC 

       > 0.1A 

Current circuit 

>600 VAC 

>7.5A/2.5mm

2

14AWG minimum 

 
 

Tools and Fasteners 

Kindly use star – type screw driver for tightening the screws. 

NOTE:

 Installation should include a disconnecting device, like switch or 

circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary 
supply (control power).The disconnecting device should be within the 
reach of the equipment and the operator

.

 

 

 

 
Dimension 

    

  

 

               

Note: All Dimensions are in mm. 

Front Panel 

 

 

   

Rear View 

   

   

  Wiring

  

  

System Type : Star/Wye

 

1. Top Display Window 
2. Bottom Display Window 
3. MENU/ ENTER/  
    HOLD/SCROLL Button 
4. MANUAL/ESC Button 
5. INC Button 
6. DEC Button 
7. RLY 

 

OD RE NN 610002   REV 02/21-06-16

 

 

Page 1 of 2 

1,2,3,4 -  R ,Y,B,N 
5 , 6     -  CBCT 
8          -  Com 
9,10     -  S1, S2 (R phase) 
11, 12  -  S1, S2 (Y phase) 
13, 14  -  S1, S2 (B phase) 
15, 16  -  NO, NC

 

 

 


background image

                  

CREATED ON: June 21, 2016

 

 

 

   Keys and Operation

 

 

     RUN Mode 

1. On power application, relay will be in NC condition for           
    approximately 10sec. 
2. During healthy condition, all the voltage parameters shall be  
    displayed with instantaneous values. Relay and relay LED will 
    be in ON or OFF condition depending on Rly ’y’ or Rly ‘n’ setting.                
3. During fault condition, type of  fault shall be displayed with 
    Relay OFF or ON Status depending on Rly ’y’ or Rly ‘n’ setting.  

   Auto mode

  

4. Once the fault is recovered, unit automatically comes back  
    to parameter display mode as mentioned in point – 2.  

   Manual mode

  

5. Once the fault is recovered, manual key to be pressed to  
     bring back display mode as  mentioned in point – 2. 

    6.  If faults are rectified before set trip delay timings of relay,  
         display will continue to show fault status. Relay status remain   
         unaltered. Press Manual key to show the parameter display. 

         Press MENU/ENTER key for 3Seconds to HOLD/SCROLL display. 

 

         When fault occurs unit display’s the following: 

Parameters 

Top 

display 

Bottom 
display 

OVER VOLTAGE 

Err 

OUOL 

UNDER VOLTAGE 

Err 

UUOL 

OVER CURRENT 

Err 

OCrt 

UNDER CURRENT 

Err 

UCrt 

OVER FREQUENCY 

Err 

O-HZ 

UNDER  FREQUENCY 

Err 

U-HZ 

EARTH LEAKAGE 

Err 

ELr 

PHASE UNBALANCE 

Phs 

UbAL 

PHASE REVERSE 

Phs 

rEU 

R PHASE FAIL 

FAIL 

P-r 

Y PHASE FAIL 

FAIL 

P-y 

B PHASE FAIL 

FAIL 

P-b 

 

 

 

MENU/ENTER/HOLD/SCROLL  Key 

RUN Mode             

: Used to select scroll/hold the  

                                  parameters.

 

PROGRAM MODE 

: Used to enter into program   

                                 mode. 
                          : used to select next parameters. 

 

INC Key 

PROGRAM Mode 

: Used to increase the values.

 

 

DEC Key 

PROGRAM Mode 

: Used to decrease the values. 

 

MANUAL/ESC Key 

RUN Mode

           : When fault recovery happens this 

key shall be used to Load ON/OFF manually.  

PROGRAM Mode

: It is used to view the previous 

parameters. 

        

       

 

    

Phase Unbalance Condition                                    

 

 To set unbalance condition for 20%. 

 

 Set 20 in unit (PUbL=20 as shown in the table). 

 

 If RY=350V, YB=450V, BY=319V in the load. 

 

 Fault is created in the unit, upper displays shows “Phs” and  

     lower shows “UbAL”. 

 

Calculations are as follows 

 

Set nVOL=415V, PUbL=20% in the unit. 
Vry=350V, Vyb=450V, Vbr=319V, Vavg= 373V 
Vry -Vavg=23V, Vyb -Vavg=77V, Vb-Vavg=54V 
Phase unbalance= (Maximum deviation / Vavg) * 100  
                               = (77/373)*100= 20 % 
 

PROGRAM  Mode

  

To enter program mode press INC & DEC key simultaneously for 4sec. 

 

  

 

                                                                                                                                                                 

Programming 

Parameters 

Range 

  Factory 

setting 

“nUOL” 

Nominal voltages: 415V 

415 

“OUOL” 

Over Voltage. Range: 5 to 100V 

030 

“UUOL” 

Under voltage. Range: 5 to 100V 

030 

“CT-P” 

CT Primary. Range: 5 to 2500A 

005 

“nCrt” 

Nominal Current. Range: 0.5-500A 

005.0 

“OCrt” 

Over Current. Range: 105-800% 

120 

“UCrt” 

Under Current. Range: 20-95% 

20 

“ 

PUbl” 

Phase Unbalance. Range: P 1-20% 

20 

“O-Hz” 

Over frequency. Range: 2 to 5Hz 

05 

10 

“U-Hz” 

Under frequency. Range: 2 to 5Hz 

05 

11 

“ELr” 

Earth leakage current. Range: 1 to 8A 

12 

“IrdY” 

Inrush delay. Range: 1-60sec 

01 

13 

“ tdOU” 

Trip delay Over Voltage. Range: 1- 250sec 

005 

14 

“ tdUU” 

Trip delay Under Voltage. Range: 1 - 250sec 

005 

15 

“ tdOC” 

Trip delay Over Current. Range: 1 - 250sec 

005 

16 

“ tdUC” 

Trip delay Under Current. Range: 1 - 250sec 

005 

17 

“tdUb” 

Trip delay Unbalance. Range: 1 – 250sec 

005 

18 

bYPS    

“OUL Y/n” 

Bypass  Over Voltage 

19 

bYPS     

“UUL Y/n” 

Bypass  Under Voltage 

20 

bYPS    

“OCt Y/n” 

Bypass  Over Current 

21 

bYPS     

“UCt Y/n” 

Bypass  Under  Current 

22 

bYPS  

“UBL Y/n” 

Bypass  Phase Unbalance 

23 

bYPS  

“OHz Y/n” 

Bypass  Over Frequency 

24 

bYPS  

“UHz Y/n” 

Bypass  Under  Frequency 

25 

 

CntL 

 

rLY ‘n’ 

Relay & Status LED  OFF in 
healthy condition 

rLY ‘Y’ 

Relay & Status LED ON in 
healthy condition

 

26 

“Auto” 

 
rst  ‘Y’ 

Auto reset enable 

“Y” 

rst  ‘n’ 

Auto reset disable 
(Manual mode) 

“n”

 

       
       Technical Specification     

     Disposition

 

                          

                                                                                

       Once the product life is over, you may send back the 

 

       unit to   EAPL for disposition              

Contact 

 

Electronic Automation Pvt. Ltd 

#20, KHB Industrial Area                                                                                                                                 
 Yelahanka, Bangalore -560064 
 Ph: +91-80-28567561/2, /42802345  
 Email:  

info@eaplindiamail.com

               

www.eaplindia.com

 

Function 

Phase Unbalance, Phase 
Reversal, Phase Failure, Under 
and Over Voltage, Under and 
Over Current, Under and Over 
Frequency, Earth Leakage 
Monitor and Control. 

System Input 

 

Input Voltage 

415V AC(3Ph-4W) 

Input Current 

Current input (AR,AY,AB) Ib=5A 

Input Frequency

 

50 Hz, 

±

 10% 

Control output 

1c/o rated for 10A @ 
250VAC/28VDC resistive load 

Power Consumption

 

5VA/ 1W 

Accuracy 

 

Voltage   

±

 4V of display value 

Current   

±

 5% of Ib 

±

 1 digit  (Ib = 5A) 

Frequency   

±

 2% of FS 

±

 1 digit 

Trip Time 

±

1% of set delay 

±

 2 sec 

Earth leakage current 

±

500mA of setting accuracy. 

General 

 

Minimum sensing current 

0.5A 

Maximum sensing current 

5A(Above 5A> Ext.CT can be 
used) 

Earth leakage Trip time delay 

5 sec Earth leakage 

Phase Failure  trip time delay 

< 5 sec 

Phase reverse trip time delay 

Instantaneous 

Frequency trip time delay 

Instantaneous 

Recovery Time 

2 sec Min 

Power On Delay 

10 sec Max 

Mode of Operation 

Auto/ Manual 

Core Balance Current 
Transformer type 

Toroidal core 

CBCT Size Internal Diameter 

100mm 

Climatic 

 

Ambient Temperature 

Operation: -10

°

 C to +55

°

 C 

Storage :    -25

°

 C to +80

°

 C  

Humidity 

MAX 85% RH @ 40

°

 C 

OD RE NN 610002   REV 02/21-06-16

 

 