SPECIFICATIONS

performance level for access control

This product complies with the following UL294 Access Control Performance 
Levels:

Destructive Attack

Level 1

Line Security

Level 1

Endurance

Level 4

Prox

Level 1

Bluetooth

Standby Power

Level 1

See the UL Listed access control unit controller installation instructions for reader 
compatibility.

environmental

Operating Temperature

-31°F to + 151°F  (-35°C to +66°C)

Humidity

86 ±3°F  

(85 ±5% at 30 ±2°C)

Ingress Protection

IP65 

(not evaluated by UL)

Positioning

Suitable for OUTDOOR use.

electrical

Power supply

Power is to be provided by a UL294 Listed,
low-voltage Class 2 power limited supply or
control panel, capable of 4 hours standby.

Voltage

+10Vdc to +16Vdc

Current

Data Voltage

Rest >4Vdc / Active <1Vdc

Data Output

Wiegand, Clock & Data, Custom Outputs

Indication

1 RGB LED
(+ RGB LED illuminated keypad to 3MIL-R11325)

Sounder

Integral speaker

3M S-Gang Keypad

3M S-Gang

3M Mullion

3M Inline

62mA

41mA

41mA

15mA

3MIL-R11325

3MIL-R11320

3MIL-R11330

3MIL-R11030

Average

100mA

  82mA

  82mA

  35mA

  Peak

Idle and Peak current at 12Vdc

Model

Part No.

dimensions

polymeric materials

Potting compound

UL R/C (QMFZ2)

Mouldings

UL746C

wiring

Wiring methods shall be in accordance with
the National Electrical Code (ANSI/NFPA70),
local codes, and the authorities having jurisdiction.

Recommended cable

BELDEN 953x (or equivalent UL listed) for Wiegand.

BELDEN 9502 (or equivalent UL listed) for RS485.

All cable and wiring must be Listed and suitable for use. 

Cable length

Up to  492 feet (150 m) from controller.

Minimum
recommended wire size

Not less than 24 AWG.

reader connections

These connections are common to all readers in
the BD series.

 1

-

0V

Supply voltage ground

 2

-

+Vdc

Supply voltage (+10Vdc to +16Vdc)

 3

-

DATA1/CLK

Wiegand or Clock/Data output

 4

-

DATA0/DAT

Wiegand or Clock/Data output

 5

-

GREEN

Green LED control input

 6

-

RED

Red LED control input

 7

-

Buzzer

Buzzer control input

 8

-

TMPR/CP

Tamper or Card Present output

 9

-

RS485-

RS485 Bus

10 -

RS485+

RS485 Bus

3M S-Gang Keypad

3M S-Gang

3M Mullion

3M Inline

4.7 x 3.0 x 0.8 in ( 120 x 76 x 21 mm )

4.7 x 3.0 x 0.8 in ( 120 x 76 x 21 mm )

3.8 x 2.1 x 0.8 in (   96 x 52 x 21 mm )

3.8 x 2.1 x 0.8 in (   96 x 52 x 21 mm )

3MIL-R11325

3MIL-R11320

3MIL-R11330

3MIL-R11030

Model

Size - Inches       ( millimetres )

Part No.

100-02643-A-DEV02

3millID - 3M Inline

3MIL-R11030

125kHz

Supra®BT LE (2.4GHz)

3millID - 3M S-Gang

3MIL-R11320

125kHz

13.56MHz

Supra®BT LE (2.4GHz)

3millID - 3M S-Gang Keypad

3MIL-R11325

125kHz

13.56MHz

Supra®BT LE (2.4GHz)

3millID - 3M Mullion

3MIL-R11330

125kHz

13.56MHz

Supra®BT LE (2.4GHz)

3millID.com   +1 303 475 4972
Specifications subject to change without notice.
©2017 3millID. All rights reserved.

100-02654-C

Please turn over for installation guidance notes

i

Mounting this reader on (or near) metal may impair 
the read range of the unit.

INSTALLATION GUIDE

Bluetooth is a registered trademark of Bluetooth SIG

Supra®BT LE

 


background image

100-02643-A-DEV02

 1

-

0V

Supply voltage ground

 2

-

+Vdc

Supply voltage (+10Vdc to +16Vdc)

 3

-

DATA1/CLK

Wiegand or Clock/Data output

 4

-

DATA0/DAT

Wiegand or Clock/Data output

 5

-

GREEN

Green LED control input

 6

-

RED

Red LED control input

 7

-

Buzzer

Buzzer control input

 8

-

TMPR/CP

Tamper or Card Present output

 9

-

RS485-

RS485 Bus

10 -

RS485+

RS485 Bus

If fitted, remove reader module 
securing screw.

Pull bottom edge of reader module 
away from the backplate, and lift up.

Mount the reader backplate to a flat 
surface using suitable hardware having a 
diameter no greater than 0.15 in (4mm).

Once the backplate has been mounted, make wire connections to 
the  reader  module  in  accordance  with  the  screw  terminal 
connections shown below, and your control panel requirements. 
Ensure the cable does not impair or prevent the reader module 
being secured.

Position the reader module, ensuring 
the top-edge fixing lugs engage 
correctly with the recesses located at 
the top of the backplate. 

Swing the bottom edge of the module 
down and forward until you feel the unit 
click shut.

Secure the reader module to the 
backplate using the M3x100mm screw 
as supplied.

1

4

2

3

5

6

7

If required, you may opt to 
use security screw.

4b

Applicable  to  3M  Inline  add-on  reader  only.  The  following  is  a 
diagrammatic representation of the wiring configuration providing a 
Bluetooth  capabaility  to  most  existing  installations.  Please  consult 
your installer and the manufacturer’s details of your existing control 
panel and access control reader.

( THIS CONFIGURATION NOT EVALUATED BY UL )

line IN

line OUT

pin

1

0V

2

+Vdc (+12Vdc)

3

N/A

4

N/A

5

N/A

6

N/A

7

N/A

8

N/A

9

RS485 -

10

RS485 +

line IN

line OUT

0V
+Vdc (+12Vdc)
N/A
N/A
N/A
N/A
N/A
N/A
RS485 -
RS485 +

existing

ACCESS

CONTROL

READER

line out from 

3M Inline

 reader

security

access

CONTROL

PANEL

3M Inline

 reader

line in from control panel

 1  2  3  4  5  6  7  8  9 10

c o m p l i a n t

R o H S

These devices comply with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions: 
(1)  this  device  may  not  cause  harmful  interference, 
and  (2)  this  device  must  accept  any  interference 
received,  including  interference  that  may  cause 
undesired operation.

Any changes or modifications not expressly approved by 
the  party  responsible  for  compliance  could  void  the 
user’s authority to operate the equipment.

These devices contains: 

FCC ID: TCZ-10103751G1

EQUIPMENT

BP21018

2AKUW-AV00
2AKUW-AV90

These  RFID  proximity  readers  comply  with 
the  essential  requirements  and  relevant 
provisions of:

EU Directive 2014/53/EC

Together  with  information  provided  by 
suppliers  and  subcontractors,  these  devices 
comply  with  the  requirements  and  relevant 
provisions of:

EU Directive 2011/65/EC.

This  symbol  on  the  product  or  on  its  packaging 
indicates that the product must not be disposed of 
with  normal  household  waste.  Instead,  it  is  your 
responsibility  to  dispose  of  your  waste  equipment 
by arranging to return it to a designated collection 
point  for  the  recycling  of  waste  electrical  and 
electronic  equipment.  By  separating  and  recycling 
your  waste  equipment  at  the  time  of  disposal  you 
will help to conserve natural resources and ensure 
that  the  equipment  is  recycled  in  a  manner  that 
protects human health and the environment.

EU Directive 2012/19/EU

These notes are provided as a general guidance for mounting, fixing and connecting 3millID - 3M series RFID 
readers. Please consult your installer and the manufacturer’s details of your control panel, when configuring 
your access security system.

GENERAL GUIDANCE NOTES                to               APPLIES TO ALL READER MODELS LISTED OVERLEAF

1

7