3M

 Motor Lead Pigtail Splice

5321, 5322, 5323 & 5324

for 5/8 kV Non-Shielded and Shielded Cables 
(Ribbon or Wire and UniShield

®

 Cables)

Instructions

Cable Size Range:

Feeder: #8 AWG – 500 kcmil

Motor Lead: #10 AWG – 500 kcmil

Copper Conductors

 CAUTION

 

 Working around energized systems may cause serious injury or death. Installation should 

be performed by personnel familiar with good safety practice in handling electrical 

equipment. De-energize and ground all electrical systems before installing product.

August 2009
78-8096-4635-5-C


background image

 

78-8096-4635-5-C

Kit Contents

3 Lug Cover

3 Cold Shrink Tube

9 Mastic Sealing Strip(s)*

3 Roll Scotch

®

 Stress Control Tape 2220

3 Bag Solvent Cleaning Cloths

3 Tube Silicone Grease

3 Rolls Scotch

®

 Linerless Rubber Splicing Tape 130C

3 Instruction Sheets

Requires Vinyl Tape that is not in kit

*Quantity varies with kit number

Kit Selection Table

Kit Number

Cable Size Range (AWG/kcmil)

Cable Insulation

O.D. Range

Max Bolt Length

Feeder

Motor Lead

5321

8 – 4

10 – 4

0.30 – 0.51 in.

1/2 in.

5322

2 – 1/0

4 – 1/0

0.43 – 0.65 in.

3/4 in.

5323

1/0 – 250

2 – 250

0.53 – 0.88 in.

1 1/4 in.

5324

250 – 500

4/0 – 500

0.75 – 1.12 in.

1 1/2 in.

Table 1


background image

78-8096-4635-5-C 

3

Instructions for 5/8 kV Pigtail Non-Shielded Feeder Cables

1.0 Prepare Cable According to Standard Procedures

NOTE: The Scotch

®

 Stress Control Tape 2220 will not be used for non-shielded cable.

1.1  Check to be sure cables fit within cable kit range as shown in Table 1.

1.2  Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, 

remove for depth of lug barrel.

2.0 Install Lugs

2.1  Install and crimp lugs per manufacturer’s direction. See back page if 3M

 Scotchlok

 Lugs are used.

2.2  Clean insulation for approximately 6" using solvent saturated cloths provided in kit.

2.3  FOR 8kV ONLY. Fill lug/insulation gaps with Scotch

®

 Linerless Rubber Splicing Tape 130C (Figure 1).

Large Lug

Small Lug

Scotch

®

 Linerless Rubber Splicing Tape 130C

Scotch

®

 Linerless Rubber Splicing Tape 130C

Figure 1

2.4  Bolt lugs together. See Table 1 for maximum bolt length. See Figure 2 for proper bolt/lug arrangement.

Large Lug

Small Lug

Bolt Should Be Inserted Thru

Hole Of Smaller Lug First

Washer

Figure 2


background image

 

78-8096-4635-5-C

2.5  FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch

®

 Linerless Rubber Splicing 

Tape 130C (Figure 3).

Scotch

®

 Linerless Rubber Splicing Tape 130C

Figure 3

NOTE: FOR 8 kV ONLY: Lug cover will be printed with 5 kV rating, but mastic layer in Step B–5 (Figure 3) 
qualifies the part as 8 kV.

3.0 Install Lug Cover

3.1  Install Lug Cover.

NOTE: The lug cover must extend over the cable insulation by a minimum of 1". For a one hole lug it will be 
greater than 1" (
Figure 4).

Lug Cover

1" Min.

 

Figure 4

3.2  Remove liner from Mastic Sealant Strips and apply around and between cables and at a position as close as 

possible to the end of the Lug Cover (Figure 5).

3.3  Overwrap Mastic Sealant and the end of the Lug Cover with one or two wraps of vinyl tape (Figure 5).

Vinyl Tape

Mastic Strips

Figure 5 


background image

78-8096-4635-5-C 

5

4.0 Install Cold Shrink Insulator

4.1  Install Cold Shrink by sliding it over the Lug Cover with the loose end tab at terminal lug end. Align the end of 

the Cold Shrink Tube approximately 2 beyond the Mastic Seal and Vinyl Seal Tape. Remove core by unwinding 
counter-clockwise (Figure 6).

TIP: An occassional tug will aid in the removal of the core.

Mastic and Vinyl

Tape Seal

Counter-Clockwise

2"

Figure 6

Instructions for 5/8 kV Pigtail Shielded Feeder Cables 

(Ribbon or Wire Shielded and UniShield

®

 Cables)

5.0 Prepare Cable According to Standard Procedures

5.1  Check to be sure cables sizes fit within cable kit range as shown in Table 1.

For Non-Shielded Motor Lead Cable

5.2  Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, 

remove for depth of lug barrel.

5.3  Clean insulation for approximately 6" using solvent saturated cloth provided in kit.

For Shielded Feeder Cable

For Ribbon Shielded Cable see Figures 7a, 8a and 9a.

For Wire Shielded Cable see Figures 7b, 8b and 9b.

For UniShield

®

 Cable see Figures 7c, 8c and 9c.

5.4  Prepare cable by removing jacket and shielding per dimensions as shown in Figures 7 and 8, depending on type 

of cable shielding.

NOTE: If practice calls for grounding shield, do not cut shield wires. See grounding.

5.5  Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, 

remove for depth of lug barrel. See Figure 7a, 7b and 7c, depending on type of cable shielding.


background image

 

78-8096-4635-5-C

1"

1/4"

3-1/2"

Depth Of

Terminal

Lug Barrel

For Ribbon Shielding

Cable Jacket

Cable Metallic Shield

Cable Semi-Conductive Material

Cable Insulation

Figure 7a

Cable Semi-Conductive Material

Cable Insulation

Cable Shield Wires

Cable Jacket

Depth Of

Terminal

Lug Barrel

3-1/4"

1-1/4"

For Wire Shielding

Figure 7b

Cable Semi-Conductive Jacket

Cable Shield Wires

Cable Insulation

Depth Of

Terminal

Lug Barrel

4"

1/2"

For UniShield

®

Figure 7c

5.6  Clean cable insulation by using solvent saturated cloths. Do not allow solvent to touch cable semi-con. If 

abrasive must be used to remove imbedded semi-con from cable insulation, use a non-conductive, 120 grit 
aluminum oxide, such as in the Scotch

®

 Cable Prep Kit CC–2 or 3M

 Abrasive Roll A–3.

6.0 Install Stress Relief

6.1  Apply two half-lapped layers of Scotch

®

 Stress Control Tape 2220 for 1/4" onto the cable semi-con (1/2" onto 

UniShield

®

 jacket) and extend two inches onto cable insulation (wrap tape silver side out). Figures 8a, 8b or 8c, 

depending on type of cable shielding.

NOTE: Grounding

If practice calls for an external ground, a 3M Ground Strap Assembly Kit (GS–1, GS–2 and GS–3) is available 
from your local distributor for use on ribbon shield cable. Follow procedure for these kits for grounding. For 
UniShield

®

 and wire shield cable, a ground strap assembly kit is not necessary. Simply fold the wires back over 

jacket to connect to the system ground.


background image

78-8096-4635-5-C 

7

Scotch

®

  Stress Control Tape 2220 

1/4"

2"

For Ribbon Shielding

Figure 8a

For Wire Shielding

1/2"

1"

2"

1/4"

Scotch

®

 Stress Control Tape 2220 

Figure 8b

1/2"

For UniShield

®

1/2"

2"

Scotch

®

 Stress Control Tape 2220 

 

Figure 8c

6.2  Wrap two half-lapped layers of vinyl tape over the Scotch

®

 Stress Control Tape 2220 and one inch onto cable 

jacket. (1/2" beyond cut off, bent back shield wires for wire and UniShield

®

 cables. Figures 9a, 9b or 9c, 

depending on type of cable shielding).

Scotch

®

 Super 33+™ Vinyl Electrical Tape

For Ribbon Shielding

1"

Figure 9a

For Wire Shielding

1/2"

Scotch

®

 Super 33+™ Vinyl Electrical Tape

 

1"

Figure 9b


background image

 

78-8096-4635-5-C

1/2"

For UniShield

®

1/2"

Scotch

®

  Super 33+™ Vinyl Electrical Tape

Figure 9c

7.0 Install Lugs

7.1  Install and crimp lugs per manufacturer’s direction; see back page if 3M

 Scotchlok

 Lugs are used.

7.2  FOR 8kV ONLY. Fill lug/insulation gaps with Scotch

®

 Linerless Rubber Splicing Tape 130C (Figure 10).

Large Lug

Small Lug

Scotch

®

 Linerless Rubber Splicing Tape 130C

Scotch

®

 Linerless Rubber Splicing Tape 130C

Figure 10

7.3  Bolt lugs together. See Table 1 on cover for maximum bolt length. See Figure 11 for proper bolt/lug 

arrangement.

Large Lug

Small Lug

Bolt Should Be Inserted Thru

Hole Of Smaller Lug First

Washer

Figure 11


background image

78-8096-4635-5-C 

9

7.4  FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch

®

 Linerless Rubber Splicing 

Tape 130C (Figure 12).

Scotch

®

 Linerless Rubber Splicing Tape 130C

Figure 12

8.0 Installation

8.1  Install Lug Cover (Figure 13).

NOTE: The lug cover must extend over the cable insulation by a minimum of 1". For a one hole lug, it will be 
greater than 1".

8.2  Remove liner from mastic sealing strips and apply around and between the cables at a position as close as 

possible to the end of the lug cover (Figure 14).

8.3  Overwrap mastic sealant and the end of the Lug Cover with one or two wraps of vinyl tape (Figure 14).

Lug Cover

1"  Min.

Figure 13

Lug Cover

Mastic Strips

Scotch

®

 Super 33+™ Vinyl Electrical Tape

Figure 14


background image

 

10 

78-8096-4635-5-C

9.0 Install Cold Shrink Insulator

9.1  Install Cold Shrink Insulator by sliding it over the Lug Cover with the loose core end tab at terminal end. Align 

the end of the Cold Shrink Insulator so it covers the vinyl tape on the feeder cable. Remove core by unwinding 
counter-clockwise (Figure 15).

TIP: An occasional tug will aid in the removal of the core.

NOTE: When starting to remove core, observe to make sure end of Cold Shrink remains lined up over the vinyl 
tape
 (Figure 15).

Lug Cover

Cold Shrink Insulator

 

Counter-Clockwise

Figure 15


background image

78-8096-4635-5-C 

11

Tooling Index

Lug and Crimping Information for 3M

™ 

Scotchlok

™ 

Copper Lugs

30014 thru 30045

One hole

31145 thru 31166

Two hole

Copper Lugs

CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS)

Cable

Size

Stud

Size

Scotchlok

Copper Lug

Number

Burndy Corporation

Thomas & Betts Corporation

Square D Co.

Anderson Div.

Size

Size

Copper Lug

Number

MD6

MY29

Y34A

Y35, Y39,

Y45*, Y46*

TBM 5

TBM 8

TBM 15

VC6-3

VC6-FT**

6

10

1/

5/164

30014

30015

30016

6 AWG (1)

U5CRT (1)

Blue (1)

Blue (1)

Universal (1)

4

10

1/4

3/8

30018

30019

30021

W161 (1) 4 AWG (1) A4CR (1) U4CRT (1)

Grey (1)

Grey (1)

Universal (1)

2

1/4

5/16

3/8

30022

30023

30024

W162 (2) 2 AWG (1) A2CR (1) U2CRT (2)

Brown (1)

Brown (1)

33 (1)

Universal (2)

1

5/16

3/8

30027

30028

1 AWG (1) A1CR (1) U1CRT (2)

Green (1)

Green (1)

37 (1)

Universal (2)

1/0

5/16

3/8

30031

30032

W163 (2)

1/0 (1)

A25R (1)

U25RT (1)

Pink (2)

Pink (2)

42H (2)

Universal (1)

2/0

3/8

30036

W241 (2)

2/0 (1)

A26R (1)

U26RT (2)

Black (2)

Black (2)

45 (1)

Universal (1)

3/0

1/2

30041

W243 (2)

3/0 (1)

A27R (1)

U27RT (2) Orange (2) Orange (2)

50 (1)

Universal (2)

4/0

1/2

1/2

30045

31145

BG (3)

BG (4)

4/0 (1)

4/0 (2)

U28RT (2)

U28RT (3)

Purple (2)

Purple (3)

Purple (2)

Purple (3)

54H (2)

54H (3)

Universal (2)

Universal (3)

250

1/2

31149

W166 (4)

250 (2)

A29R (2)

U29RT (3)

Yellow (2)

Yellow (2)

62 (2)

Universal (2)

300

1/2

31153

A30R (2)

U30RT (3)

White (3)

66 (3)

Universal (3)

350

1/2

31156

A31R (2)

U31RT (3)

Red (4)

71H (4)

400

1/2

31160

A32R (2)

U32RT (3)

Blue (4)

76H (4)

500

1/2

31166

A34R (2)

U34RT (3)

Brown (4)

87H (4)

Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.

**Anderson VC6*3 and VC6*FT require no die set.

3M


background image

3M and Scotchlok are trademarks of 3M Company. Scotch is a registered trademark of 3M Company. 
UniShield is a registered trademark of General Cable Technologies Corporation.
Important Notice
All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, 
but the accuracy or completeness is not guaranteed.

 

Before using this product, you must evaluate it and determine if it is suitable for 

your intended application.

 

You assume all risks and liability associated with such use.

 

Any statements related to the product which are not 

contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless 
expressly agreed upon, in writing, by an authorized officer of 3M.
Warranty; Limited Remedy; Limited Liability. 
This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase.

 

3M MAKES NO 

OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR 
A PARTICULAR PURPOSE.

 

If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's 

option, to replace or repair the 3M product or refund the purchase price of the 3M product.

 

Except where prohibited by law, 3M will 

not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of 
the legal theory asserted. 

3

Electrical Markets Division

6801 River Place Blvd. 

Austin, TX 78726-9000 

800-245-3573

Fax 800-245-0329

www.3M.com/electrical

Please Recycle. Printed in USA.

© 3M 2009. All Rights Reserved.

78-8096-4635-5-C